Analisa Pengaruh Pembebanan untuk Peramalan Umur Trafo Study Kasus pada PT. PLN UP3 Surabaya Barat

Trisna Wati, Fiqih Bayu Saputra, Fariz Isyraqi, Yoga Sukryawan

Abstract

In the five distribution transformers operating in 2020–2022, the load has increased in each period. At the RA 1208 substation, the load during the day is 9.7% and 8.33% at night. The RA 1218 substation has a load during the day of 6.47% and 4.15% at night. RB substation has loads of 5.93% during the day and 6.55% at night. The RA 1220 substation gets loads of 4.78% during the day and 4.13% at night. RA 977 substation obtains loads of 7.27% during the day and 6.02% at night. Load improvement, causing heat and loss of life, is influenced by ambient temperature, where the average daily temperature in Surabaya reaches 29°C to 30°C. In order to make the transformer at PLN Ltd. UP3 in West Surabaya work properly, it is necessary to predict the transformer’s life. This study employed linear and exponential trends, with the MAPE evaluation test and impact analysis of the loading on the transformer's remaining life referring to IEC standards. At substation 1208 and using an exponential trend of 1.2597%, the remaining life forecast for 2032 is 7.92 years. Substation 1218, using an exponential trend of 1.2361%, has a remaining life forecast of 10.81 years. With an exponential trend of 1.1048%, substation RB 1503 gains a remaining life forecast of 10.52 years. Substation 1220, using an exponential trend of 1.2057%, gets a remaining life forecast of 10.95 years. Substation RA 977, using the exponential trend of 1.6338%, has a remaining life forecast of 6.46 years.

Keywords

distribution transformer; linear trend; exponential trend; life los

Full Text:

PDF

References

M. Suyanto, R. Setyowibowo, and P. E. Pambudi, “Evaluasi Kemampuan Transformator Daya Pada Gardu Induk 150 Kv Wates,” J. Teknol. Technoscienta, vol. 10, no. 2, pp. 202–208, 2018.

Y. Y. Rizki and E. Ervianto, “Perkiraan umur transformator berdasarkan pengaruh pembebanan dan temperatur lingkungan menggunakan metode trend linear,” Jom Fteknik, vol. 6, no. 2, pp. 1–8, 2019.

H. L. Latupeirissa, “Analisa Umur Pakai Transformator Distribusi 20 KV,” J. Simetrik, vol. 8, no. 2, pp. 139–144, 2018.

Zulkarnaini and H. Riandi, “Analisa Peramalan Beban Listrik Di RSUP Dr . M . Djamil Padang Sampai Tahun 2029,” MENARA Ilmu, vol. XIV, no. 01, pp. 134–145, 2020.

F. Azhar, Y. Rahmawati, and I. Fadlika, “Estimasi Umur Transformator Distribusi Berdasarkan Pertumbuhan Beban dan Temperatur Lingkungan di Penyulang Bolo PLN Rayon Woha Kabupaten Bima,” Semin. Nas. Inov. dan Apl. Teknol. di Ind., pp. 43–49, 2019.

P. G.-J. T. E. U. Tanjungpura and undefined 2017, “Studi Susut Umur Transformator Distribusi 20 KV Akibat Pembebanan Lebih di PT. PLN (Persero) Kota Pontianak,” jurnal.untan.ac.id,Accessed:Jan.27,2022.[Online].Available:https://jurnal.untan.ac.id/index.php/jteuntan/article/view/21155.

Refbacks